What’s the Difference Between Back-Siphonage and Back-Pressure?

  • bill57931
  • 54 minutes ago
  • 5 min read
ree

Keeping your drinking water safe starts with preventing backflow—unwanted reverse flow of water or contaminants into your clean supply. Two terms often come up in backflow prevention: back-siphonage and back-pressure.


While they both lead to contamination risk, they happen for different reasons and require targeted solutions. In this guide, Atlas Backflow Services breaks down the differences in plain language, shares real-world examples, and explains how to stay compliant with the Backflow Testing Orange County experts recommend.


Quick Definition: Backflow 101


  • Backflow: Any reversal of water direction that pulls or pushes non-potable water into your potable (drinking) supply.

  • Back-siphonage: A reverse flow caused by negative pressure (a vacuum or suction effect) on the supply side.

  • Back-pressure: A reverse flow caused by higher downstream pressure pushing water back into the supply.


Both are dangerous. The key difference is what drives the reversal—suction vs. push.


Back-Siphonage Explained: When Suction Pulls Contaminants In


Back-siphonage happens when the pressure in the public or building supply drops below the pressure in your system, creating a vacuum that literally sucks water backward.


Common causes:


  • Water main breaks or hydrant use creating sudden negative pressure

  • High-demand events (firefighting, nearby construction)

  • Elevated tanks or systems draining too quickly

  • Improper hose connections submerged in buckets, pools, or chemical sprayers


Real-world scenarios:


  • A garden hose left in a fertilizer sprayer when the city main depressurizes—fertilized water gets siphoned into your home’s lines.

  • Commercial kitchen sinks with spray nozzles below the flood rim pulling dirty sink water into the potable line during a pressure dip.


Best defenses for back-siphonage:


  • Air gaps (the gold standard for high hazard cross-connections like commercial dishwashers and chemical tanks)

  • Pressure Vacuum Breakers (PVBs) or Spill-Resistant Vacuum Breakers (SVBs) on irrigation systems

  • Proper hose bibb vacuum breakers on outdoor spigots


When we perform the Backflow Testing Orange County experts recommend, we pay special attention to vacuum breaker performance and air gap integrity because these are your frontline protections against back-siphonage.


Back-Pressure Explained: When Downstream Pressure Pushes Back


Back-pressure occurs when the water (or fluid) on the user side becomes higher pressure than the supply and forces its way back into the potable line.Common causes:


  • Booster pumps or elevated systems creating greater downstream head pressure

  • Closed or partially closed valves that trap pressure downstream

  • Thermal expansion in water heaters without proper expansion tanks

  • Pressurized chemical feed systems in industrial/process settings


Real-world scenarios:


  • A commercial boiler without a proper backflow preventer heating water and building pressure past the municipal supply—heated, chemically treated water can get pushed into the city line.

  • An irrigation pump boosting pressure in a landscape system and driving non-potable water back toward the main.


Best defenses for back-pressure:


  • Reduced Pressure Zone assemblies (RPZ/RPBA) for high-hazard applications (chemicals, boilers, commercial processes)

  • Double Check Valve Assemblies (DCVA/DCDA) for low-hazard situations like some fire sprinkler systems

  • Correctly sized thermal expansion tanks and pressure controls


Back-pressure risks can be significant, which is why Atlas Backflow Services often recommends RPZ protection for critical cross-connections and verifies performance during the Backflow Testing Orange County experts recommend.


Back-Siphonage vs. Back-Pressure: The Core Differences


  • Cause

    • Back-siphonage: Supply side pressure drops; suction pulls water backward.

    • Back-pressure: Downstream pressure rises; pushes water backward.

  • Typical Devices

    • Back-siphonage: Air gaps, PVBs, SVBs, hose vacuum breakers.

    • Back-pressure: RPZs for high hazard, DCVAs for low hazard.

  • Common Triggers

    • Back-siphonage: Main breaks, firefighting flows, sudden demand.

    • Back-pressure: Pumps, boilers, thermal expansion, elevation changes.

  • Risk Profile

    • Both can introduce contaminants; selection of device depends on hazard level and how the reversal could occur.


Where You’ll Encounter Each in Orange County


  • Irrigation systems: Vulnerable to both. PVB/SVB helps with back-siphonage; RPZ may be required if fertilizers/chemicals are injected.

  • Fire sprinkler systems: Often require DCDA (double check detector assembly); some high-hazard configurations need RPZ.

  • Commercial kitchens & food service: Air gaps on dish machines; RPZs where chemicals or carbonators exist.

  • Boilers and water heaters: Thermal expansion and treatment chemicals raise back-pressure risk—often RPZ protected.

  • Car washes, salons, labs, breweries: Elevated risks due to pumps and chemicals; RPZ protection is common.


Our team at Atlas Backflow Services evaluates each use case and local code requirements, then performs the Backflow Testing Orange County experts recommend to keep you compliant and protected.


How to Prevent Both Problems: Practical Steps


  • Know your cross-connections: Identify every spot where potable and non-potable waters could meet.

  • Choose the right device:

    • High hazard or chemical exposure: RPZ

    • Low hazard containment: DCVA

    • Irrigation with back-siphonage risk: PVB/SVB

    • Absolute protection at fixtures: Air gap

  • Install correctly:

    • Respect elevation requirements (e.g., PVB above highest downstream outlet).

    • Protect from flooding, freezing, and backflow outlet submergence.

  • Test annually (or as required):

    • Many Orange County jurisdictions mandate annual testing by certified testers.

    • Document results for water purveyor and compliance audits.

  • Maintain proactively:

    • Replace worn check valves, relief valve parts, and rubber components as needed.

    • Keep areas clear for access; don’t enclose devices without proper drainage and clearance.


When in doubt, schedule the Backflow Testing Orange County experts recommend with Atlas Backflow Services—we’ll verify device performance, spot code issues, and provide repair or rebuild options on the spot.


Signs You May Have a Backflow Problem


  • Noticeable taste, odor, or discoloration in tap water

  • Pressure fluctuations or air in lines after a nearby main event

  • Dripping relief ports on RPZs or failed test readings

  • Irrigation water appearing in indoor lines, or cross-connection incidents after renovations


If you experience any of the above, shut off the suspected line and call a certified tester immediately. Our technicians handle emergency assessments and the Backflow Testing Orange County experts recommend to resolve the issue quickly.


Compliance in Orange County: What to Expect


  • Many water purveyors require:

    • Annual testing by a certified backflow tester

    • Test reports submitted to the city or water district

    • Repairs within a set timeframe if a device fails

  • Property types affected:

    • Commercial properties, multifamily buildings, fire lines, irrigation with chemical injection, food service, and more

  • Atlas Backflow Services can:

    • Track your renewal dates

    • Perform testing, repairs, and replacements

    • File all reports with your water purveyor


This turnkey approach ensures you get the Backflow Testing Orange County experts recommend—without the paperwork headache.


Frequently Asked Questions


  • Do I need an RPZ or a DCVA?

    • It depends on hazard level. High hazard (chemicals, boilers, potential health risks) typically requires an RPZ. Low hazard may allow a DCVA. We’ll assess your site and local code.

  • Is an air gap better than a valve?

    • For back-siphonage, air gaps provide maximum protection, but they’re not always practical. Many systems combine air gaps with valve-based protection.

  • How often should I test?

    • Most Orange County jurisdictions require annual testing, sometimes more frequently for high-risk systems or after repairs/installation.


Protect Your Water with Atlas Backflow Services


Whether your risk is back-siphonage, back-pressure, or both, the right device and regular testing are non-negotiable for safety and compliance. Atlas Backflow Services provides certified inspections, repairs, replacements, and the Backflow Testing Orange County experts recommend—all tailored to your property and local code.Ready to schedule or need a quick assessment?


Contact Atlas Backflow Services today and keep your water safe, compliant, and flowing the right way.

 
 
 

Sunday

AVAILABLE BY APPOINTMENT or for emergencies, call (NO TXT) (562)343-1436 or txt (562)-304-3069 24 hrs a day

WORKING HOURS

Monday - Friday

7:00AM - 4:00PM for emergencies, call (NO TXT) (562)343-1436 or txt (562)-304-3069 24 hrs a day

Saturday

AVAILABLE BY APPOINTMENT or for emergencies, call (NO TXT) (562)343-1436 or txt (562)-304-3069 24 hrs a day

VISIT US

ATLAS BACKFLOW INC.

2852 Gundry Avenue, Signal Hill CA 90755

Office: (562) 343-1436 

Cell: (562) 304-3069

 

(Call or Text 24 hr's a day)

C-36 #1088210

  • Yelp
  • Facebook

GET IN TOUCH

Thanks for submitting!

© 2025 | Atlas Backflow Services

bottom of page